CPACINC.COM

Computer and IT Solutions Professionals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOOP / PSC TESTER

MODEL TES-1800
  • Large custom high contrast display.
  • Auto lock out if test resister overheats.
  • Voltage indication.
  • Measure low loop with 0.01W resolution.
  • High loop range permit measurement
    of ground spikes.
  • Microprocessor controlled.

TES-1800
Specification¡G
Loop Impedance Range 20 / 200 / 2000W
Loop Impedance Accuracy +/- ( 2% + 2dgts ) at 1W on 20W Range
Lowest Resolution 0.01W
Voltage Display +/- 2% + 1digit
Ac Test Current 25A nominal at 20 Range
Ac Test Period 20ms
PSC Range 200A / 2000A / 20KA
Operating Voltage 230V +/- 10% , 50Hz +/- 1 %
Withstand Voltage 3000V AC for 1 minute
Fuse Protection HRC ceramic fuse
Dimensions 200(L) ¡Ñ 140(W) ¡Ñ 95(H)mm
Weight Approx. 900g
Display 3 digit liquid crystal display with a maximum reading
of 1999.
Over Range Indication " OL " will be shown on the LCD
Penal when out of range measurement is made.
Operating Temperature and Humidity 0oC to 40oC (32oF to 104oF), Below 80% RH
Storage Temperature -10oC to 60oC (14oF to 140oF)
Over Temperature " OL " on " " in display
Accessories Test Lead with IEC Connector