Specifications¡G
Measuring Range and Accuracy ( at 23oC and 45-75%RH
)
|
Function
|
Measuring range
|
Accuracy
|
Overload Protection
|
|
Earth Voltage
|
0 ~ 399.9V (50Hz,
60Hz)
|
+/- (1%rdg+4dgts)
|
400Vrms / 1 minute
|
Earth Resistance
|
0 ~ 39.99W
|
+/- (2%rdg+0.2W)
|
250Vrms / 10 seconds
|
|
0 ~ 399.9W
|
+/- (2%rdg+3dgts)
|
|
0 ~ 3999W
|
Current Consumption
( typical Value with battery voltage of 12V )
|
Range
|
ON
|
|
40W/ 400W/4000W
|
42mA
|
|
Earth V
|
22mA
|
General Specification:
¡° Safety Standard : IEC1010-1 overvoltage category III
, IEC 61557
¡° Display : 3 3/4 digit liquid crystal display with a maximum
reading of 3999.
¡° Insulation Resistance : More than 5MW between the circuit
and the housing case when
measured with 500VDC
¡° Withstand Voltage : 3700CV AC for 1 minute between the
circuit and the housing case.
¡° Timer (Auto power off) : about 3 minutes.
¡° Dimensions : 190(L) ¡Ñ 140(W) ¡Ñ 77(H)mm
¡° Weight : Approx. 800 (with battery)
¡° Power Source : Eight 1.5V 01t AA Size Battery.
¡° Over range Indication : " OL " will be shown on the LCD
Penal when out of range
measurement is made.
¡° Operating Temperature and Humidity : 0oC to
40oC (32oF to 104oF) ,
below 80% RH
¡° Storage Temperature : -10oC to 60oC
(14oF to 140oF)
¡° Accessories : Test leads Auxiliary--> 1 Set , Auxiliary
earth spikes--> 2 Pieces ,
Neck strap--> 1Piece , Batteries, AA, R - 6P or equivalent-->
8 Piece
|